Automatic circuit breaker for wide variety of applications. Designed to protect electrical users in residential and non-residential buildings as a part of electrical distribution system, as well as in low-voltage industrial switchgears. AP50B circuit breakers conduct current in regular mode and cut-off current in case of overload or short-circuit, and also can be switched off and on manually.
Device is compliant with GOST 9098-78
Technical parameters
AP50B 2T | AP50B 2M | AP50B 2MT | AP50B 1M2TD | AP50B 3T | AP50B 3M | AP50B 3MT | AP50B2M3TN | AP50B 2MN | AP50B 2M3TD | AP50B 2M3TO | AP50B 3M3TS | ||
Two-pole | Three-pole | ||||||||||||
Rated current, A | 1.6, 2.5, 4.0, 6.3, 10, 16, 25, 40, 50, 63 | 16..63 | 2.5..63 | ||||||||||
Rated AC voltage, V | up to 500 | ||||||||||||
Rated DC voltage, V | up to 220 | - | - | - | - | - | - | - | - | - | |||
Trigger overcurrent, I/IRATED | - | 3.5 and 10 | - | 3.5 and 10 | 10 | ||||||||
Release element type | |||||||||||||
Electromagnetic | - | +(2) | +(2) | +(1) | - | +(3) | +(3) | +(2) | +(2) | +(2) | +(2) | +(3) | |
Thermal | +(2) | - | +(2) | +(2) | +(3) | - | +(3) | +(3) | - | +(3) | +(3) | +(3) | |
Under-voltage | - | - | - | - | - | - | - | + | + | - | - | - | |
Shunt | - | - | - | + | - | - | - | - | - | + | - | - | |
Over-current in neutral wire | - | - | - | - | - | - | - | - | - | - | + | - | |
Control circuit | - | - | - | - | - | - | - | - | - | - | - | + | |
Accessories | |||||||||||||
Auxiliary contacts (2p), (1p) | 2p(1p) | 2p(1p) | 2p(1p) | 1p | 2p(1p) | 2p(1p) | 2p(1p) | 2p(1p) | 2p(1p) | 1p | 2p(1p) | 2p(1p) | |
Extra shell (IP54) | + | + | + | + | + | + | + | + | + | + | + | + | |
Mass, kg | |||||||||||||
Without extra shell, up to, kg | 1 | 1.3 | |||||||||||
With extra shell, up to, kg | 2.2 | ||||||||||||
Rated current, A | ||||||||||
1.6 | 2.5 | 4 | 6.3 | 10 | 16 | 25 | 40 | 50 | 63 | |
Ultimate breaking capacity, kA | ||||||||||
AC circuit, 380 V | 0.3 | 0.4 | 0.6 | 0.8 | 2.0 | 3.0 | 3.0 | 5.0 | 5.0 | 5.0 |
AC circuit, 500 V | 0.3 | 0.4 | 0.6 | 0.8 | 1.5 | 1.5 | 2.5 | 2.5 | 2.5 | 2.5 |
AC circuit, 220V | 0.5 | 0.7 | 1.0 | 1.4 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 |
Durability | ||||||||||
Switching, on-off cycles | 20000 | 16000 | 10000 | |||||||
Total, on-off cycles | 30000 |