Intermediate electromagnetic relay for electric motor drive control systems. Suitable for AC with voltages up to 400 V and frequencies 50/60 Hz and DC circuits with voltages up to 220 V.
Operational conditions
Altitude, m | 2000 |
Ambient air temperature, oC | -40..+55 |
Environment requirements | nonexplosive, no dust in quantities interfering with relay operation, no corrosive gases and vapors in metal and insulation damaging quantities |
Vibration frequency, Hz acceleration, not more than, g |
1..35 0.5 |
Operating position | vertical or horizontal, maximum verticality deviation 5o |
DC relays allow rectified power supply. Allowed voltage ripple, not more than | 8% |
Annotation breakdown
PE-37-XX-X3
PE-37 – relay type
XX – contacts layout
X – climate version (U – boreal, T – tropical)
3 – location environmental class
Technical parameters
Coil rated voltage, V | DC | 12; 24; 48; 60; 110; 220 | |
AC 50 Hz | 12; 24; 36; 40; 110; 127; 220; 230; 240; 380; 400; 415 | ||
Contact circuit rated voltage, V | DC | 12..220 | |
AC | 12..400 | ||
Contact rated current, A | 6 | ||
Number of contacts | 2; 6; 8 | ||
IP rating | operating mechanism | IP 20 | |
terminals | IP 00 | ||
Actuation time, not more than, ms | 50 | ||
Releasing time, not more than, ms | 50 | ||
Mechanical durability, millions of switching cycles | 16 | ||
Power consumption, not more than | DC, W | 4.0 | |
AC, VA | 7.0 | ||
Mass, not more than, kg | 0.68 |