Relay for DC (up to 320 V) and AC (up to 418 V 50..2400 Hz) circuits.
Can be used in critical circuits of fixed and mobile equipment, including surface-mounted equipment, shipbuilding, aircraft, nuclear power stations, etc.
Technical parameters
Rated control circuit voltage, V | 12; 24; 27; 110; 220 |
Minimum switching current, A | 0.001 at voltage not less than 30 V 0.5 at voltage not less than 20 V 1 at voltage not less than 6 V |
Voltage drop at contacts (current 0.5 A..rated), not more than, V | 0.6 |
Operation modes | continuous, periodic, intermittent, short-time |
Switching frequency, hour-1 | 1200 |
Durability (depending on operation mode), number of cycles | up to 100000 |
Switching power DC AC |
96..1600 W 660..12000 VA |
Relay mounting method | screw |
Wire mounting method | soldering |
Climate version | all-climate |
IP rating terminals relay |
IP00 IP40 |
Version | Number of contacts | Rated current per contact, A | Mass, not more than, kg | |
front | break | |||
RNE66 | 6 | 6 | 10 | 0.225 |
Rated control circuit DC voltage, V | Coil resistance at +20 oC, Ohm |
12 | 21±2.1 |
24 | 83±8.3 |
27 | 108±10.8 |
110 | 1460±146 |
220 | 5600±560 |